How to Wire an Elektrogas Proof of Closure Device

We’ve created a video demonstration to help users wire a DIN plug for an Elektrogas Proof of Closure device. The numbers in this blog correspond with the numbers in the video.

1. Once you’ve unscrewed the plug and removed it from the proof of closure device, step one is to remove the rubber gasket and set it aside. 

2. Next, remove the screw. You will alternately push and pull the screw out of the plug. The inside of the plug isn’t threaded, so you don’t need to use a screwdriver in this step.

3. You will need a small, flat-bladed screwdriver to pop the connection block out of the plug housing.

4. The connection block is where you will install your wires. Push the wires through the plug housing before installing them to the connection block.  Use your small screwdriver to loosen the screws you find on the connection block — all except the one marked with the Ground symbol.

DIN plug schematic
Schematic also appears in the video

Schematic

5. This is the drawing found in the Elektrogas literature. The designations found on the right; 1, 2, 3, and COM, correspond to the markings on the connection block.

One is hot, Two is “valve open,” Three is “valve closed,” and the terminal marked “COM” is neutral in this case

The connection block contains a two-tone LED, to provide visual indication of the valve’s position. Once wired, powered, and connected to the proof of closure device, a red light means the valve is open; a green light means the valve is closed.

With the wiring complete, it’s time to reinstall the connection block in the plug housing. Feed the wires back through the plug housing until you can pop the connection block in place.

6. Proper installation of these three components keeps moisture from entering the plug housing. The rubber gasket must come first, followed by the metal washer, and finally the nylon nut. When using SO cord, keep openings in the insulated jacket on the terminal side of the rubber gasket. Any cuts in the insulated jacket which are on the other side of the gasket will allow moisture to enter the plug housing.

 Replace the screw and gasket to complete your plug assembly. 

For automation

Visit olstrad.com to learn more about our automation processes!

Posted by  b-olstrad ; Published June 3, 2022

 Categories: Elektrogas, FAQs

 Tags: , , ,

 Bookmark the permalink

 RSS Feed (comments for this post)

Both comments and trackbacks are currently closed.

 
 

Combustion 911

600 Mogadore Rd. Kent, OH 44240

Phone 330-678-3683

Email: support_ab@combustion911.com

View Terms and Conditions

Privacy Policy

©2024 Olstrad Engineering All Rights Reserved

Visit Combustion 911 on LinkedInVisit Combustion 911 on FacebookVisit Combustion 911 on TwitterWatch Combustion 911 videos on YouTubeEmail Combustion 911Read Articles on the Combustion 911 Blog
Olstrad Corporation
ESA Industrial Burners IHEA Member Elektrogas Valves and Regulators

Need a quote? Have a Question?